ZPS Pure Full Sine Wave Inverter

Created by: Super User

Features:

  • Pure sine wave output, available for sensitive load
  • 4-step progressive charging, 7 battery type selector
  • Fast and powerful charger with 30A and 70A
  • Accept generator’s energy output
  • High power factor
  • Automatically transfer between battery and line modes
  • Microprocessor control guarantees high reliability
  • Bypass without battery connected
  • Remote control function

Protection against:

  • Over load, over temperature, over charging, low battery
  • Reverse connection(optional by hard connector)
  • blackouts

Model No.

ZPS-1KW

ZPS-2KW

ZPS-3KW

ZPS-4KW

ZPS-5KW

ZPS-6KW

Nominal Power

1000W

2000W

3000W

4000W

5000W

6000W

AC Input

Phase & waveform

Single phase & sine wave

Voltage

120VAC/230VAC

Acceptable Voltage

194-243VAC\164-243VAC(wide mode

Line Low Transfer

85V±4%/184(154 wide mode±4%)

Line Low Return

95V±4%/194(164 wide mode±4%)

Line high Transfer

135V±4%/253±4%

Line high Return

127V±4%/243±4%

Frequency

50Hz or 60Hz (auto sensing)

Line Low Transfer

47Hz for 50Hz,57Hz for 60Hz

Line high Transfer

55Hz for 50Hz,65Hz for 60Hz

Output      

Phase & waveform

Single phase & sinewavebypass mode sync to input

Voltage

230VACbypass mode sync to input

Voltage Regulation

±10%rmsbypass mode sync to input

Frequency

50Hz±0.3Hzbypass mode sync to input

Crest Power

3 times of ratings

Short Circuit Protection

Yes,shutdown after 10 minutes

Power Factor

0.9-1.0

DC Input      

Battery Voltage

12V/24V

12V/24V/48V

24V/48V

Minimum Start Voltage

10V for 12V,20V for 24V,40V for 48V

Low Battery Alarm

10.5V for 12V,21V for 24V,42V for 48V

Low Battery Transfer

10V for 12V,20V for 24V,40V for 48V

High Voltage Alarm

16V for 12V,32V for 24V,64V for 48V

Max Charging Current

70A\35A

Over Charge Voltage

15.7V for 12V,31.4V for 24V,62.8V for 48V

Transfer Efficiency      

line Mode

95%

Battery Mode

88%

power saver

Available when the load is less than 25 Watts

Indicators

7-LED Display

From the right to the left,LED1 line mode (green lighting)LED2 inverter mode
(green lighting)
LED3 charging modeyellow lighting)、LED4 Fully charged 
(green lighting)
LED5 over heat shutdown(red lighting)、LED6 Overloaded 
shutdown
red lighting)、LED7 Saving Modegreen lighting

3-LED Display

Charging Mode(green lighting)inverter mode(green lighting) Alarmred lighting

Switch selector

Saving Mode is on/off when push the switch forwards/backwards, keeping it horisontal is 
turning the inverter off.
    

Audible Alarm

Sounding when the heatsink's tem is over 105 an

Dimension,D X W X H(mm)

218X179X442

 218X179X598

 

Inverter Output

Model

ZPS-8.0KW

ZPS-10.0KW

ZPS-12.0KW

Continuous Output power

8.0KW

10.0KW

12.0KW

Surge Rating (20ms)

24.0KW

30.0KW

36.0KW

Output Waveform

Pure Sine wave/Same as input(Bypass Mode)

Nominal Efficiency

>88%(Peak)

Line Mode Efficiency (Line Mode)

>95%

Power Factor

0.9-1.0

Nominal Output Voltage rms

100-110-120Vac/220-230-240Vac

Output Voltage Regulation

±10% RMS

Output Frequency

50Hz±0.3Hz/60Hz±0.3Hz

Short Circuit Protection

Yes(1 sec after fault)

Typical transfer Time

10ms(Max)

THD

<10%

DC Input

Nominal Input Voltage

12.0Vdc

(*2 for 24Vdc,*4 for 48Vdc)

Minimum Start Voltage

10.0Vdc

Low Battery Alarm

10.5Vdc/11.0Vdc

Low Battery Trip

10.0Vdc/10.2Vdc

High Voltage Alarm

16.0Vdc

Low Battery Voltage recover

16.5Vdc

Idle Consumption-Search Mode

<25W when Power Saver On

Charger

Output Voltage

Depends on battery type

Charge Breaker Rating

40A

40A

40A

Max Charge Power Rate(1/3 Rating Power)

1/3 Rating Power

Battery Initial Voltage for Start Up

10-15.7V for 12V(*2 for 24V,*4 for 48V)

Over Charge Protection Shutdown

15.7V for 12V(*2 for 24V,*4 for 48V)

Remote Control

Yes(Optional)

Bypass & Protection

Input Voltage Waveform

Sine wave(Grid or Generator)

Nominal Voltage

220Vac

230Vac

230Vac

Max Input AC Frequency

150VAC For 120Vac LV Mode;300VAC For 230Vac HV Mode

Nominal Input Frequency

50Hz or 60Hz(Auto detect)

Low Freq Trip

47Hz±0.3Hz for 50Hz,57Hz±0.3Hz for 60Hz

High Freq Trip

50Hz±0.3Hz for 50Hz,60Hz±0.3Hz for 60Hz

Overload protection (SMPS load)

Circuit breaker

Output Short circuit protection

Circuit breaker

Bypass breaker rating

50A

63A

63A

Transfer switch rating

40 amp for UL

80 amp for UL

Bypass without batttery connected

Yes(Optional)

Max bypass current

40amp

80amp

Mechanical Specification

Mounting

Wall Mount

Inverter Dimensions (L*W*H)

588*415*200

Inverter Weight (Solar Chg)KG

60+2.5

66+2.5

70+2.5

Shipping Dimensions (L*W*H)

750*520*310

Shipping Weight (Solar Chg)KG

62+2.5

68+2.5

72+2.5

Display

Status LEDs/Status LEDs+LCD